Complete Gearbox & Geared Motor Solutions

Technical guide

What Data a Gearbox Selection Needs for Frequent Start-Stop and Reversing Duty

Author: CHINFAR Technical Team · Reviewer: Tinyuen (CHINFAR) · Updated: 2026-11-04

CHINFAR modular geared motor

Frequent start-stop and reversing duty is not covered by adding a start count to the power figure you already have. Three independent input groups must each be filled in far enough for the band to be identified: work-machine type with daily loaded running time, starts per hour with daily loaded running time, and ambient temperature where an S series unit is involved. If any group cannot be placed, a supplier can only ask back. That is a hard stop in the workflow, not a courtesy question.

Why a start count on its own cannot be used

A bare "20 starts per hour" cannot enter a selection, because it is missing the other dimension of the same judgement: daily loaded running time.

Twenty starts per hour with one hour of loaded running a day and twenty starts per hour with twenty hours of loaded running a day are not comparable cases. The first unit spends most of its life cooling down; the second has almost no cooling window at all. Starts per hour and loaded running time sit in the same group for exactly this reason — neither carries usable information without the other.

It also explains why selection tables band the two together instead of listing two figures that can be reported independently. If either dimension cannot be placed in a band, the total duty factor cannot be established. That is a hard block in the process, and treating it as a formality is how a wrong model gets onto a purchase order.

The six inputs a selection needs, and the three duty groups behind them

At minimum, six items have to be on the table:

#InputWhat it fixesIf it is missing
1Product series (R/F/K/S, H/B or P)Which coefficient set and selection table appliesNo table to work from
2Work-machine typeThe base band, including whether the reversing row appliesOnly a request back for duty details
3Daily loaded running timeThe band, jointly with starts per hourBand cannot be fixed
4Starts per hourThe band, jointly with loaded running timeBand cannot be fixed
5Running power P (kW)Torque at the output of the gear reducerTorque cannot be calculated
6Target output speed n2, or the ratio iOutput speed and reduction ratioNo selection possible

Items 2 to 4 carry the first two of the three duty groups: work-machine type with loaded running time, and starts per hour with loaded running time. The third group is ambient temperature, which applies only where an S series geared motor is specified — R/F/K series do not use it.

One point is worth stating plainly: the duty factor is not a single number. It is built from three components — one from the work-machine type together with daily loaded running time, one from starts per hour together with daily loaded running time, and for the S series one from ambient temperature. A total exists only once every applicable component has been placed in a band, and even a complete total stays a candidate until each participating component has been reviewed. A candidate total is not a commitment.

How the duty is usually reported, and how it has to be reported

This is the most practical part of the page. The same physical situation, written two ways, decides whether a selection can be made at all.

What is usually writtenProblemWhat should be written
"20 starts per hour"No loaded time, so the band cannot be fixed"20 starts per hour, 8 hours loaded per day"
"Runs all day"Continuous and intermittent loading cannot be told apart"8 hours loaded, 16 hours idle per day"
"It reverses"No reversing frequency, and no word on whether reversal happens under load"Reverses every 2 minutes, under load"
"Heavy duty"Heavy duty is a conclusion, not an inputGive the work-machine type and the load spectrum
A power number onlyNot stated whether this is the motor rating or the actual running powerSay whether it is running power or installed power
"It needs to run slower"No selection possibleGive the target output speed n2 or the ratio i
"Normal ambient"The S series needs an actual temperatureGive the maximum ambient temperature

Band boundaries belong to the reviewed current catalogue and are not restated here. Tables differ between series and between editions, and a boundary copied across from the wrong one is worse than no boundary at all.

Reversing is a separate row in the work-machine classification, not an extra multiplier

Reversing is not an additional factor applied on top of a non-reversing result. It is a separate row in the work-machine classification.

In the duty factor table the same kind of equipment appears more than once: one row for the version without reversing, another row for the version with it. Reversing therefore enters through the class the work machine is placed in. Nothing is multiplied on afterwards, and there is no single reversing coefficient that could be laid over a no-reversing figure. A buyer and a supplier who treat it as a multiplier are not simply disagreeing about the numbers; they are working from different rules.

Two practical consequences follow:

  1. State at inquiry time whether the drive reverses. Report a start count, leave reversing out, and the machine is classified into the wrong row — the result is then wrong in a way that no later arithmetic repairs.
  2. Give the reversing frequency together with the load state at the moment of reversal. "Reverses every 2 minutes, under load" and "reverses twice a day, at no load" are different duties, even where the start count per hour is identical.

Referring load inertia to the motor shaft, and the torque it takes to accelerate

In frequent start-stop duty the accelerating and decelerating phases often demand more torque than steady running does. Two inputs are needed to calculate that torque: load inertia and acceleration time.

Refer the load inertia to the motor shaft first:

J_total = J_motor + J_load / i²

J_motor is the rotor inertia of the motor, J_load is the load-side inertia referred to the load shaft, i is the ratio of the speed reducer, and the unit throughout is kg·m². The larger the ratio, the smaller the load inertia seen at the motor shaft — it decays with the square of the ratio. That is one practical reason planetary and multi-stage units hold up well in frequent start-stop duty.

Then the angular acceleration:

α = 2π · Δn / (60 · Δt)

Δn is the change in speed in rpm, Δt is the acceleration or deceleration time in s, and α comes out in rad/s².

And from those two, the acceleration torque:

T_acc = J_total · α

T_acc is in N·m. It has to be added to the steady-state load torque before it means anything: the sum is the instantaneous torque the gearbox has to deliver while the drive accelerates. This is also where the warning sits — if the torque quoted by the supplier covers steady state only, while the acceleration time is squeezed very short, this term is the real bottleneck in the selection. A torque figure silent about the accelerating phase is not evidence that the accelerating phase is safe.

Equivalent thermal load: the quantity that blocks frequent-start selections

Most inquiries watch peak torque and miss the quantity that more often decides the case: heat.

Every start-stop cycle carries an acceleration and a deceleration in which torque sits above the steady-state value. Duty of this kind produces heat faster than continuous running at the same power, and the higher the start frequency, the larger the share of the cycle spent accelerating. Engineering judges the cycle by its equivalent thermal load:

T_rms = √( Σ T_i² · t_i / Σ t_i )

T_i is the torque of segment i in N·m, t_i is the duration of segment i in s, and the summation runs over the whole working cycle. Squaring the torque weights the short high peaks, and dividing by total time spreads them back across the cycle, so what comes out describes heating rather than instantaneous shock.

Two checks follow, and both are needed:

  • Peak check — the maximum instantaneous torque, T_acc included, must not exceed the allowable peak of the selected model.
  • Thermal check — the cycle-equivalent thermal load must not exceed the allowable continuous output of the selected gear reducer, with ambient temperature and cooling conditions taken into account.

Running the peak check and skipping the thermal check is the most common selection mistake in frequent start-stop duty. The allowable values behind both checks have to be confirmed by the supplier for the specific model and cooling arrangement.

Braking method decides where the energy goes

Reversing and frequent stopping both involve braking, and the braking method determines what the kinetic energy becomes and where the heat appears.

Braking methodWhere the kinetic energy goesWhere the heat appearsWhat must be stated to the supplier
Mechanical braking (spring-applied brake)Converted to heat by frictionThe friction pair of the brakePermissible braking work of the brake, braking frequency, stopping time
Variable-frequency braking (dynamic braking)Dissipated in the braking resistorThe braking resistorBraking unit rating, resistor power, duty cycle
Regenerative brakingReturned to the DC bus or to the supplyThe drive and the regeneration unitRegenerative capacity, grid conditions, whether regeneration is permitted

The point to hold on to: where the energy goes is where the heat appears. If most of the braking falls on a mechanical brake, the permissible braking work and the permitted braking frequency are inputs the supplier must confirm for the model — they cannot be assumed by the buyer. Writing the braking task off as "the gearbox will self-lock" is neither valid nor safe: reversing and frequent-stop duty need a braking scheme of their own.

Condition-by-condition judgement

Duty conditionMain riskData still neededRecommended action
High starts per hour with long daily loaded timeHeat accumulation, unit selected too smallBands for both starts per hour and loaded timeRun the peak and thermal checks together
Reversing under load, reversal frequentBidirectional shock adds up; classification lands in the wrong rowReversing frequency, load state at reversalMark the reversing row explicitly and give the reversing parameters
Acceleration time squeezed very shortAcceleration torque exceeds steady-state torqueLoad inertia, acceleration timeSupply the inertia and recheck T_acc
High-inertia load (fans, flywheels, long conveyors)Referred inertia still demands large acceleration torqueJ_load and the ratioRefer through J_total = J_motor + J_load / i², then recheck
Braking duty falling on the mechanical brakeBrake overheating, fast wear of the friction pairBraking work, braking frequency, stopping timeSupplier confirms permissible brake values for the model
High ambient temperature (S series especially)The thermal check basis shiftsMaximum ambient temperature, cooling methodSupply the ambient value and recalculate on a thermal balance
Load direction includes radial or axial componentsBearings loaded beyond the allowableMagnitude, point of application, overhung distanceNo availability commitment before the dimensions are reviewed

Site checklist

Observable while running

  1. The actual share of loaded versus idle time within one complete working cycle.
  2. Actual starts per hour — read it from a counter, do not estimate it.
  3. Whether reversal happens under load, and whether there is noise or impact at reversal.
  4. Whether motor current during acceleration is clearly above the steady-state level.

Requires shutdown

  1. Record the motor nameplate and the actual running power, keeping installed power and running power apart.
  2. Measure or obtain the load-side moment of inertia; where no figure exists, give the geometry and mass of the load so that it can be estimated.
  3. Record the acceleration time — the actual time from command to reaching the target speed.
  4. Confirm the brake type, the braking frequency and the actual stopping time.
  5. Confirm the maximum ambient temperature and the cooling method (natural, fan, forced ventilation).

Must be handled by qualified personnel

  1. The final judgement on the peak and thermal checks, and confirmation of the permissible braking work of the brake.
  2. Review of the braking and fall-arrest design wherever personnel safety is involved — self-locking of the gearbox is not a substitute.

Common mistakes and where this article stops

Common mistakes

  1. Reporting starts per hour without the daily loaded running time.
  2. Treating "it reverses" as a remark, with no reversing frequency and no load state at reversal.
  3. Assuming reversing needs a multiplier on the factor — it is a separate classification row within the work-machine type.
  4. Running the peak torque check and stopping there, with no thermal check.
  5. Using installed power in place of the actual running power.
  6. Not knowing the load inertia, and not supplying the geometry and mass from which it could be estimated.
  7. Leaving the braking task to "the gearbox self-locking", or assuming a brake can brake an unlimited number of times.

Where this stops

  • The input list, the classification logic and the formulas here apply to frequent start-stop and reversing duty on R/F/K/S modular geared motors, H/B industrial gearboxes and P series planetary gearboxes.
  • No duty factor value, no start-per-hour limit, no inertia limit and no braking-frequency limit are given, and no band boundary is restated. Those come from the reviewed current catalogue and from engineering confirmation.
  • The formulas state variable relationships and units only. They must be rechecked against actual duty data before they are used to support a selection conclusion.
  • This article does not replace a functional safety design for a specific machine.

Data checklist to send a supplier

#Data itemNote
1Product seriesR/F/K/S, H/B or P
2Work-machine typeAs specific as possible; state whether it falls into a reversing category
3Daily loaded running timeIn hours, including the share of idle time
4Starts per hourA measured value, not an estimate
5Running power PkW; running power distinguished from installed power
6Target output speed n2 or ratio iEither one is enough
7Ambient temperatureMandatory for the S series, advisable for the others
8Whether reversing is requiredIf so, add the reversing frequency and the load state at reversal
9Braking method and stopping timeMechanical, variable-frequency or regenerative, with the stopping time
10Load inertia and acceleration timeWithout an inertia figure, give the load geometry and mass
11Mounting method and shaft loadRadial and axial loads, overhung distance where present

About this article and the publisher

This article was written by the technical team of Chengfa Reducer (Changzhou) Co., Ltd. (CHINFAR) and released after technical review. The H/B series industrial gearboxes and P series planetary gearboxes referred to above are supplied by Chengfa Reducer (Changzhou) Co., Ltd., and products are delivered through the joint manufacturing system shared with HUIGUANG.

Related products and technical material:

Next step

Send the eleven items above to sales@chinfar.com. If one of them is not available yet, say that it is not available instead of putting in an estimate — a missing item can be asked back and filled in, while a wrong estimate puts the classification straight into the wrong row. Selection conclusions are subject to engineering review; this article does not replace a selection calculation for a specific duty.

Related resources

Get selection support